Explosion-Proof Motors · VE-Ex series
VE-Ex 280S
Increased-safety (Ex e) motors for Zone 1 and Zone 2 where a lighter, non-flameproof construction is acceptable.
Explosion-proofII 2G Ex e IIB T3 GbIE3IP56
Suitability is confirmed at the installation
The equipment marking above states what this machine is certified for. Whether it is suitable for a specific installation is determined by the area classification and confirmed by the responsible engineer — not by this page.
Technical data
Full specification
Attributes marked as family-specific are recorded for this product family only. Hover a label for its definition.
Identification
- Series
- VE-Ex
- Frame size
- 280S
Electrical data
- Rated power
- 90 kW
- Rated voltage
- 690 V
- Frequency
- 50 Hz
- Rated speedF
- 985 rpm
- Number of polesF
- 6
- Efficiency classF
- IE3
- EfficiencyF
- 94 %
- Power factorF
- 0.84
- Rated currentF
- 95.5 A
- VFD operationF
- No
Mechanical data
- Mounting arrangement
- IM B3
- Construction
- Horizontal
- Mass
- 690 kg
- Overall dimensions
- 1040 × 560 × 620 mm
- Rotor typeF
- Squirrel cage
Protection and cooling
- Degree of protection
- IP56
- Cooling method
- IC 411
- Ex markingF
- II 2G Ex e IIB T3 Gb
- Type of protectionF
- Ex e (increased safety)
- Gas / dust groupF
- IIB
- Temperature classF
- T3
- Equipment protection levelF
- Gb
- Permitted zoneF
- Zone 1
Operating conditions
- Climatic version
- U1 (temperate)
- Duty type
- S1
Same series
Other frame sizes in VE-Ex
Variants share the design, the certification route and the documentation. Only the rating and the frame differ.
Documentation
- Download (mock)CatalogueExplosion-Proof Motors — Product CataloguePDF · 8.4 MB · Rev. 04
- Download (mock)Data sheetVE-Ex Series — Data SheetPDF · 0.9 MB · Rev. 02
- Download (mock)CertificateIECEx Certificate of Conformity — VE-ExPDF · 1.9 MB · Issue 2
- Download (mock)QuestionnaireTechnical Questionnaire — Electric MotorsPDF / online form · 0.3 MB · Rev. 02